Learning Objectives
You will be able to:
- Accomplish the necessary preparation for inplace inspections of dc motors.
- Perform a static inspection in accordance with the manufacturer's technical manual
and applicable NAVSEA technical manuals.
- Conduct the appropriate mechanical tests.
- Conduct the necessary electrical tests: insulation resistance, isolation of dc
windings, and circuitry.
- Accomplish inplace operational tests for a dc electric motor.
|
Background
You could be called upon to investigate an installed electric motor that has
intermittent operational problems or is not operating at all. In most cases, you will be
required not only to diagnose the problem but to actually accomplish onsite repairs or
take action to have repairs accomplished as required.
During this lesson, we will discuss some of the inspections and repair procedures that
you must know to properly inspect, troubleshoot, and repair a dc motor.
Determining the cause of electrical motor problems is usually more difficult than
finding mechanical problems. But, as in any type of troubleshooting, your senses of smell,
sight, and hearing are your best tools. In cases of electrical problems, it will be
necessary to use generally approved troubleshooting procedures.
Preparation for static inspection
Contact tended unit personnel to obtain as much information as possible about the
operating history of the motor, information about the failure, and other pertinent
information. Examples of some questions to ask are:
Did the motor fail during operation?
Did the motor fail to operate during initial startup after maintenance?
Was the motor overheating, arcing at the brushes, smoking, or frequently
tripping the overloads?
Has maintenance been performed recently on the system or equipment with which
the motor is associated?
Ensure
that the power supply is tagged out by tended unit personnel.
Inspect the controller to determine if the overloads are tripped. Use a voltmeter to
test incoming power leads in the controller to ensure that power has been secured. Remove
inspection covers from the motor.
Static inspection
Inspect the commutator for evidence of excessive arcing, blackening, burned
spots, flat spots, threading, high or low bars, high mica, or a burned ring around the
commutator.
A commutator in unsatisfactory condition will require inplace stoning or
armature removal to facilitate turning in a lathe. No action should be taken until all
electrical tests have been performed on the armature and field windings. Faulty armature
or field windings can directly affect commutator appearance and condition. Refer to NSTM
Chapter 300 (series), paragraph 5.4.3.6, for guidance o
.
Inspect brushes for proper length, tension, freedom of movement in brush
holders, contact surface, and frayed or broken shunts.
Inspect brush holders for condition of springs, evidence of arcing, and
their distance from the commutator.
Brush
holders should be set 1/16 to 1/8 inch from the commutator surface.
Inspect accessible armature and field windings. Also, inspect insulation
for evidence of overheating, burned spots, bare conductors, or mechanical damage. Pay
particular attention to the condition of interconnections between field windings and their
connection points.
Inspect windings for cleanliness and evidence of carbon dust, grease, oil,
and salt deposits.
Inspect the power cable in the vicinity of the motor connection box for
signs of burned or deteriorated insulation, discoloration, or breaks in the cable.
Mechanical tests

Do NOT rotate the armature backwards (opposite to its normal
direction of rotation); severe brush damage could result.
Rotate the motor shaft by hand, if possible. Check for freedom of rotation, rubbing, or
binding. Some brush drag can be expected. Check for excessive end or side play. Secure
testing if the motor appears to be binding. Disassemble the motor if the cause of the
binding cannot be determined.
Refer to the manufacturer's technical manual and the lesson on inplace repair of dc
motors if disassembly is necessary.
Commutator
runout readings larger than 0.003 inch total indicated runout will require turning in a
lathe.
If the mechanical condition of the motor appears to be satisfactory, conduct a
commutator runout test in accordance with procedures listed in the lesson on inplace inspection of dc motors (mechanical).
Insulation resistance test of motor windings
Test
line leads in the controller with a voltmeter to ensure that power has been secured.
A
reading must be conducted on all commutator segments. This can sometimes be accomplished
more quickly by wrapping a piece of solder around the commutator and twisting the ends
together. The insulation resistance reading can then be taken on the twisted ends.
Prepare for the test by consulting the manufacturer's technical manual to
determine internal and external armature and field connections. This ensures that
conducting an insulation resistance test on the commutator will read all motor windings.