JQR251.16 Armature Undercutter

Back
Previous Page

251.16

Back to 200 Level Training

Inplace Inspection of DC Motors Electrical (Continued)


Testing field windings

Field windings will be tested for opens, shorts, and grounds. The type of motor and the internal and external connections will dictate the amount of isolation necessary.

Refer to motor drawings in the manufacturer's technical manual or the controller diagram before starting to isolate the field windings. Information required will pertain both to types of connections and the internal resistance of the field windings.

Testing the shunt field

note.gif (1021 bytes) For purposes of this portion of the lesson, we will assume ground readings have been taken and that we are testing a compound motor.

Use a low-reading ohmmeter, Kelvin bridge, or Wheatstone bridge to test for opens and shorts. The figure at right shows standard compound motor terminal markings and connections.

note.gif (1021 bytes) The shunt field leads are normally the smallest diameter leads in the motor connection box. They can be quickly identified in this manner if not marked.

Test the shunt field for opens and shorts by reading across the F1 and F2 or F1 and A2 leads in the connection box.

Compare internal resistance readings to those listed. The total shunt field reading will normally be only a few ohms. If the resistance value of only one field winding is listed, it will be necessary to multiply by the number of windings in series to determine the approximate total internal field resistance.

A very high or infinity reading will indicate an open field winding, open connection box leads, or open winding interconnection lead(s).

Take corrective action if readings are not satisfactory. This will include comparison readings of individual windings and replacing or rewinding faulty winding(s).

Testing series field/interpoles

note.gif (1021 bytes) The series field windings and interpole (IP) windings, if applicable, will sometimes be internally connected in series between the A2 connection box lead and the A2 terminal on the brush rigging.

Test the series field for opens and shorts by reading across S1 and S2 leads in connection box, if applicable.

note.gif (1021 bytes) The armature lead that runs from the brush rigging to the series field or interpole windings is normally designated A2. The lead from the motor connection box to the brush rigging is normally designated A1. The armature leads (A1 and A2) can be identified in this manner if unmarked.

In cases where only the A2 lead is brought out to the connection box, test the series field and interpoles, if applicable, by readings across the A2 connection box lead and the A2 lead on the brush rigging.

If necessary, disconnect lead A2 from the brush rigging or lift brushes from the commutator prior to reading series field/interpoles. Continuity of the A1 lead can now be read between A1 in the connection box and the incoming brush rigging lead connection point.

Compare internal resistance readings to those listed. The total series field/interpole reading will normally be less than 1 ohm. Determine total design internal resistance in the same manner as per shunt field.

A very high or infinity reading will indicate an open series field or interpole winding, open connection box leads, or open winding interconnection lead(s).

If necessary, take the same corrective action as for the shunt fields.

Testing the armature

The armature will be tested for opens, shorts, and grounds by the bar-to-bar method.

The endbell on the commutator end may require removal to allow for complete access to the commutator. Refer to the manufacturer's technical manual and the lesson on inplace repair of dc motors for disassembly procedures.

The alternate inplace bar-to-bar test procedure below can be accomplished if motor accessibility permits.

Lift or remove all brushes except for one set of positive and one set of negative brushes (adjacent sets). Apply battery potential to the brushes.

caution.gif (1040 bytes)Use the same circuit configuration as in the shop method.

Test between the adjacent bars spanned by the brushes. Test between alternate bars, if necessary. Rotate the armature to place untested bars between the brushes.

Continue this procedure until all bars have been tested. Analyze the results. Take corrective action, as necessary, after completion of the bar-to-bar test.

Operational test

If results of all tests are satisfactory, an operational test will be conducted.

Reassemble the motor as necessary. Reconnect and insulate motor leads. Reconnect motor leads in the controller, if applicable. Inform personnel responsible for the driven unit that the motor is to be operated. Have tended ship's personnel conduct tag-in and reenergize the power supply.

note.gif (1021 bytes) Incoming voltage should be ±5 percent of rated voltage.

Test incoming voltage to the controller to determine if it is correct. Take action to determine the cause of improper voltage, if it is present.

Motor test run

caution.gif (1040 bytes)Secure the motor if heavy arcing is present, motor speed seems too fast or slow, or if unusual noise or vibration is present.

Start motor at no load, if possible. Observe operation. Pay particular attention to the commutator and brushes.

If there is a malfunction, take action to determine the cause. Inspect the brushes for contact and tension. Ensure that the brushholders are set 1/16 to 1/8 inch from the commutator surface. Inspect the controller for proper operation.

Conduct a no-load current test, if applicable, with a dc clamp-on ammeter. Compare the reading to information listed in the manufacturer's technical manual or on the motor nameplate.

Test-run the motor for 15 minutes at no-load condition. Observe motor operation as previously discussed. Secure the test immediately if improper operation is noted or suspected.

Have a full load applied to the motor. Conduct current reading with a dc clamp-on ammeter. Compare the readings as previously discussed.

Clean the commutator with a canvas wiper, if necessary, and if the test run is progressing satisfactorily. Run the motor at full load for 15 minutes and observe its operation.

If tests prove satisfactory

Have the circuit secured and tagged out by tended unit personnel.

Replace the connection box cover.

Inform tended unit personnel that the motor can be placed back in service.

If tests prove unsatisfactory

Further testing/disassembly will be necessary if any tests or motor operation prove unsatisfactory. Refer to the lesson on inplace repair of dc motors.

Click on image to enlarge.
eer372.gif (45219 bytes)

Standard DC Compound Motor Terminal Markings and Connections


Review Questions
If you can correctly answer the questions below, you have learned the key points in this lesson. Choose the correct answer for each question, then look at your score below the questions. Review the lesson if you miss any questions.

1. What is a maximum radial runout for a commutator?
0.3 in.
0.03 in.
0.003 in
0.0003 in.

2. How far should brush holders be from the commutator?
1/4 to 1/2 in.
1/8 to 1/4 in.
1/16 to 1/8 in.
3/32 to 1/16 in.

3. The bar-to-bar test is used to find grounds and shorts in ........
dc motor armatures.
dc motor interpoles.
shunt fields.
series fields.

4. The nomograph is used to ........
measure armature resistance.
compensate for commutation.
balance the series and shunt fields.
compensate the megger readings for temperature.

5. Which lead runs from the series field or interpole windings?
A1
A2
S1
S2

Score =
Correct answers:

Back